MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-HC25VA
MUZ-HC35VA
MUZ-HC35VAB
10 5 9.52 6.35
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
5 m 6 m 7 m 8 m 9 m 10 m
MUZ-HC25VA
MUZ-HC35VA
MUZ-HC35VAB
1,150
0 0 0 90 120 150
Calculation: X g = 30 g/m (Refrigerant piping length (m) - 5)
NOTE : Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.