Mitsubishi FR-S500 Instruction Manual Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 99
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
36
Operation by the start command of the terminal block
(external operation)
REMARKS
To make a reverse rotation start, Pr. 63 "STR terminal function selection" must be set to "---".
The motor will not rotate ... Why?
Check that [EXT] is lit.
[EXT] is valid when Pr. 79 = "0" (factory setting).
Use to lit [EXT].
Check that wiring is correct. Check once again.
Change the frequency (60Hz) of the maximum value of potentiometer (at 5V)
Adjust the frequency in Pr. 38 "frequency setting voltage gain frequency".
(Refer to page 43)
Change the frequency (0Hz) of the minimum value of potentiometer (at 0V)
Adjust the frequency in calibration parameter C2 "frequency setting Voltage
bias frequency". (Refer to Instruction Manual (detailed).)
PU
EXT
Page view 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 98 99

Comments to this Manuals

No comments