4.2 Run and operation
4.2.1 Parts of the operation panel
The operation panel cannot be removed from the inverter.
REMARKS
When the parameter unit (FR-PU04) is used, operation from the operation panel is not
accepted. ( is valid)
RUN
PU
EXT
MODE SET
RUN
PU
EXT
STOP
RESET
Used to change the setting mode.
RUN
RUN indication
PU indication **
Lit to indicate PU
operation mode.
3-digit monitor LED
Shows the frequency,
parameter number, etc.
EXT indication **
Lit to indicate external
operation mode.
Setting dial
(Setting dial: Mistubishi inverter's dial)
Used to change the frequency
setting and parameter values.
This dial cannot be removed.
MODE Key
SET Key
Used to define each setting.
When the start command is given and the frequency command
is less than the strating frequency.
reset an alarm.
STOP/RESET Key
Used to give the forward
rotation run command.
Use Pr. 17 to set reverse
operation.
RUN Key
Used to switch between the
PU and external operation
mode. When using external
operation mode (operation
using the separately
connected frequency setting
potentiometer and start
signal), press this key to
light up the EXT indication.
(Change the Pr. 79 value to
use the combined mode.)
PU: PU operation mode
EXT: External operation mode
PU/EXT Key
Turns on/flickers* to indicate operation.
* RUN indication
On: Indicates that forward rotation operation is being performed.
Slow flickering (1.4s cycle): Indicates reverse rotation
Fast flickering (0.2s cycle): Indicates that operation is not being performed
but the was pressed or the start command was given.
** PU/EXT indication
Flickers slowly in the computer link operation mode.
STOP
RESET