3
1
CONNECTION OF PERIPHERAL DEVICES (BASIC CONFIGURATION)
1. CONNECTION OF PERIPHERAL DEVICES (BASIC
CONFIGURATION)
Power supply
Use within the permissible power supply specifications
of the inverter. (Refer to page 80.)
Moulded case circuit breaker or earth leakage
circuit breaker
The breaker must be selected carefully since an in-rush
current flows in the inverter at power on.
Magnetic contactor
Install for your safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will cause the
inverter life to be shorten. (Refer to page 18.)
Installation of a reactor
A reactor must be used when the power harmonics
measure is taken, power factor is to be improved or the
inverter is installed near a large supply system (500kVA
or more and wiring distance within 10 m).
Make the selection carefully.
Devices connected to the output
Do not install a power factor correction capacitor, surge
suppressor or capacitor type filter on the output side of the
inverter.
When installing a moulded case circuit breaker on the
output side of the inverter, contact each manufacturer for
selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the
motor and inverter.
For reduction of induction noise from the power line of
the inverter, it is recommended to wire the earth
(ground) cable by returning it to the earth (ground)
terminal of the inverter.
(For details of noise reduction techniques, refer to the
instruction manual (detailed).)
(MC)
(MCCB)
or (ELB)
AC reactor
(FR-HAL
/FR-BAL)
DC reactor
(FR-HEL
/FR-BEL)
Inverter
(FR-S500E)
Motor
Earth (Ground)
Earth (Ground)Earth (Ground)
Inverter
The life of the inverter is influenced by ambient
temperature. Check the ambient temperature.
Epecially when mounting the inverter inside an
enclosure, take cautions of the ambient temperature.
(Refer to page 85.)
Wrong wiring might lead to damage of the inverter.
The control signal wires must be kept fully away from the
main circuit to protect them from noise. (Refer to page 7.)