Adjustment (calibration) of the frequency meter (indicator)
5.2
Adjustment (calibration) of the frequency meter (indicator)
Changing example Deflecting the meter (analog indicator) to full-scale (1mA) at the preset
frequency of 60Hz.
(Refer to page 24 for frequency setting.)
POINT
The calibration parameters "C1" can be made to be read by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "FM terminal calibration".
REMARKS
Depending on the set value, it may take some time for the needle to move.
If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "FM
terminal calibration" can also be set in external operation mode.
POINT
By setting the Pr. 54 "FM terminal function selection" value, preset Pr. 55
"frequency monitoring reference" or Pr. 56 "current monitoring reference" to the
running frequency or current value at which the output signal is 1440 pulses/s.
At 1440 pulses/s, the meter generally deflects to full-scale.
By turning the , you can read another parameter.
Press the to return to the " " indication (step 3).
Press the twice to show the next parameter ( ).
1.
2.
3.
8.
7.
6.
5.
4.
Press the to choose the parameter
setting mode.
MODE
Press the to enable setting.
SET
SET
SET
SET
Turn the to show " " setting.
Press the to show " ".
SET
MODE
SET
Press the .
Flicker...Parameter setting complete!!
Setting is complete.
If the inverter is at a stop, press the
to start the inverter.
(A motor need not be connected.)
RUN
PU
EXT
RUN
RUN
Turn the to adjust the indicator
needle to the desired position.
Pr. 30 must be set to "1".
(For details, refer to steps 3 to 6 on
.)
The parameter
number read
previously appears.
Analog indicator
Operation
SET
SET
Display
Turn the until the calibration parameter
C1 "FM terminal calibration" appears.
page 51