Changing the output frequency setting of the frequency setting
potentiometer (bias and gain of frequency setting voltage (current))
5
ADJUSTMENT OF THE FREQUENCY SETTING POTENTIOMETER AND INDICATOR
(2) Adjusting a deviation of the highest frequency from the Pr. 38 (Pr. 39) setting.
(2)-1)Making adjustment with a voltage applied directly across terminals 2-5
(with a current flowing across terminals 4-5)
Changing example
Changing the calibration parameter C4 "frequency setting voltage gain"
POINT
The calibration parameter C4 is an extended function parameter. Pr. 30 must
be set to "1".
The frequency meter (indicator) connected to across terminals FM-SD does not
indicate just 50Hz ... Why?
The calibration parameter C1 "FM terminal calibration" value must be set.
(Refer to page 46.)
When write is performed, an error ( ) is displayed.
The gain and bias frequency settings are too close.
Turn the until " " appears.
Operation
RUN
PU
EXT
1.
PU
EXT
(Press the
.)
Confirm the RUN indication and operation
mode indication.
The inverter must be at a stop.
The inverter must be in PU operation mode.
3.
MODE
2.
MODE
SET
4.
SET
Press the
7.
1
2
3
4
5
6
7
8
9
10
*
*
The value is nearly 100 (%) in the maximum
position of the potentiometer.
8.
Press the
to set the value.
SET
SET
*
Flicker ... Parameter setting complete!!
5.
Turn the
until the calibration parameter
C4 "frequency setting voltage gain" appears.
6.
SET
SET
Analog voltage
value (%) across
terminals 2-5
Press the
to show the analog voltage
value (%).
(Adjustment complete)
*
The value is nearly 100 (%) in the maximum position
of the potentiometer.
Apply a 5V voltage.
(Turn the external potentiometer
connected to across terminals
2-5 to the maximum (any position).)
Press the
to choose the parameter
setting mode.
By turning the , you can read another parameter.
SET
Press the to return to the " " indication (step 4).
SET
Press the twice to show the next parameter ( ).
(For details, refer to steps 3 to 6 on .)
Pr. 30 must be set to "1".
to show .
" "
When adjusting Pr. 38
After performing operation in step 7, do not touch the until completion of calibration.
CAUTION
Display
The parameter
number read
previously appears.