Mitsubishi City Multi PMFY-P.VBM-E Specifications Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 69
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
Control
The New Remote Controller PZ-60DR-E enable simple control setting
Centralized Controller System
LOSSNAY independent
Interlocked with Air conditioners
Interlocked with City Multi Interlocked with Mr.Slim
City Multi
M-NET transmission line
Mr.Slim LOSSNAY
RX
5
LOSSNAY
RX
5
Slim-LOSSNAY connection cable
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY remote
controller
PZ-60DR-E
can be connected
LOSSNAY RX
5
(Max 15 unit)
PZ-52SF-E can be used insted of PZ-60DR-E,
However, function is limited and connecting
position is different.
The LOSSNAY remote controller (PZ-60DR-E,
PZ-41SLB-E) can not be used with this system.
PZ-41SLB-E can be connected however function
is limited.
Centralized controller
AG-150A
Power supply unit
(PAC-SC51KUA)
Outdoor unit
Network remote
controller
Mr.Slim
remote controller
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY remote
controller
PZ-60DR-E
Mr.Slim
outdoor unit
Mr.Slim
indoor unit
Network remote
controller
LOSSNAY
RX
5
LOSSNAY
RX
5
LOSSNAY
RX
5LOSSNAY
RX
5
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY
RX
5
Ext. signal source
LOSSNAY remote
controller
PZ-60DR-E
Interlocked with
City Multi indoor units
Interlocked with
Mr. Slim indoor units
LOSSNAY units only
Interlocked with
external devices
Indoor unit Indoor unit
Page78
LOSSNAY
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-100RX
5-E
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
2.3-2.4
500-535
1000
278
16.3-17.3
160-170
80.0
72.5
71.0
36-37
2.1-2.1
445-475
1000
278
10.2-11.2
100-110
80.0
72.5
71.0
34-35
1.7-1.7
350-380
755
210
5.6-6.1
55-60
83.0
74.0
73.0
31-32.5
0.9-0.9
175-200
415
115
1.8
18
87.0
80.0
79.0
21-22
Extra High High Low Extra Low
2.3-2.4
510-550
1000
278
16.3-17.3
160-170
37-38
2.1-2.1
460-485
1000
278
10.2-11.2
100-110
35-36
1.7-1.7
365-395
755
210
5.6-6.1
55-60
32-33
0.9-0.9
175-200
415
115
1.8
18
21-22
59
Under 4.6 A Less
*The Air outlets noise (45 angle, 1.5 meters in front of the unit) is about 17 dB greater than the indicated value. (at High Fan speed)
Frequency / Power source
50Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-150RX
5-E
LOSSNAY ventilation By-pass ventilation
105
Under 7.3 A Less
Extra High High Low
3.5-3.5
760-830
1500
417
16.3-17.8
160-175
80.0
72.0
70.5
38-39
3.2-3.2
690-740
1500
417
13.3-13.8
130-135
80.0
72.0
70.5
36-37.5
2.9-2.9
630-680
1300
361
9.7-10.2
95-100
81.0
72.5
71.5
33.5-35
Extra High High Low
3.5-3.5
765-835
1500
417
16.3-17.8
160-175
39-40.5
3.2-3.2
695-745
1500
417
13.3-13.8
130-135
37.5-39
2.9-2.9
635-685
1300
361
9.7-10.2
95-100
35.5-37
*The Air outlets noise (45 angle, 1.5 meters in front of the unit) is about 19 dB greater than the indicated value. (at High Fan speed)
Frequency / Power source
50Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-200RX
5-E
LOSSNAY ventilation By-pass ventilation
118
Under 11.9A Less
Extra High High Low
4.8-4.8
1035-1100
2000
556
16.3-16.8
160-165
80.0
72.5
71.0
39.5-40
4.2-4.2
910-980
2000
556
10.2-10.7
100-105
80.0
72.5
71.0
37-38
3.4-3.4
715-785
1580
439
6.1-6.6
60-65
83.0
73.5
72.0
32.5-34
Extra High High Low
4.8-4.8
1040-1110
2000
556
16.3-16.8
160-165
40.5-41
4.2-4.2
915-980
2000
556
10.2-10.7
100-105
38-39
3.4-3.4
720-785
1580
439
6.1-6.6
60-65
33.5-35
*The Air outlets noise (45 angle, 1.5 meters in front of the unit) is about 20 dB greater than the indicated value. (at High Fan speed)
Frequency / Power source
50Hz / Single phase 220-240V
LGH-100RX5-E
LGH-150RX
5-E
LGH-200RX
5-E
Page77
Indoor unit
Page view 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 68 69

Comments to this Manuals