Mitsubishi City Multi PMFY-P.VBM-E Specifications Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 69
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
GUF - For the finest indoor quality
GUF = [ LOSSNAY ] + [ HEATING & COOLING ]
RDH3 SERIES
OUTDOOR AIR PROCESSING UNIT GUF type
General
Specification
Lossnay (Energy Recover)
DX Coil(Heating & Cooling)
GUF model image
Model
Power source
Cooling capacity
Figure in < > is the recovery
capacity by LOSSNAY core.
Heating capacity
Figure in < > is the recovery
capacity by LOSSNAY core.
Capacity equivalent to indoor unit
Humidifying capacity
External finish
External dimension H W D
Net weight
Heat
exchanger
FAN
Noise level (Low-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Diameter of
refrigerant pipe
Diameter of drain pipe
kW
kcal / h
BTU / h
kW
A
kW
kcal / h
BTU / h
kW
A
kg / h
lbs / h
mm
in.
kg (lbs)
Pa
mmH
2
O
kW
m
3
/ h
L / s
cfm
dB <A>
mm (in.)
mm (in.)
mm (in.)
1
1
1
2
2
2
Power input
Current input
Power input
Current input
Humidifier
LOSSNAY core
Refrigerant coil
Type Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(High value)
Supplying air
Exhausting air
Liquid
Gas
GUF-50RDH3 GUF-100RDH3 GUF-50RD3 GUF-100RD3
235-265
1.15
235-265
1.15
P32
2.7
6.0
317 1,016 1,288
12-1/2 40 50-3/4
57 (126)
125
12.7
-
500
139
294
33.5-34.5
ø6.35 (ø1/4) Flare
ø12.7 (ø1/2) Flare
480-505
2.20
480-505
2.20
P63
5.4
12.0
398 1,231 1,580
15-11/16 48-1/2 62-1/4
98 (217)
135
13.8
-
1,000
139
589
38-39
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
235-265
1.15
235-265
1.15
P32
-
-
317 1,016 1,288
12-1/2 40 50-3/4
54 (120)
140
14.3
-
500
139
294
33.5-34.5
ø6.35 (ø1/4) Flare
ø12.7 (ø1/2) Flare
480-505
2.20
480-505
2.20
P63
-
-
398 1,231 1,580
15-11/16 48-1/2 62-1/4
92 (203)
140
14.3
-
1,000
139
589
38-39
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
1-phase 220-240V 50Hz, 1-phase 220V 60Hz
Galvanized, with grey insulation sheet
Partition, Cross-flow structure, Special preserved paper-plate.
Cross fin (Aluminum fin and copper tube)
SA: Centrifugal fan (Sirocco fan) 1
EA: Centrifugal fan (Sirocco fan) 1
Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2units
Direct-driven by motor
Polyester sheet
Non-woven fabrics filter (Gravitational method 82%) & Optional part: High efficiency filter (Colorimetric method 65%)
Non-woven fabrics filter (Gravitational method 82%)
Fuse
LEV
VP25
Permeable film humidifier
-
<1.83>
<1,600>
<6,200>
<2.01>
<1,700>
<6,900>
5.46
4,700
18,600
6.18
5,300
21,100
11.17
9,600
38,100
12.50
10,800
42,700
<3.85>
<3,300>
<13,100>
<4.20>
<3,600>
<14,300>
<1.83>
<1,600>
<6,200>
<2.01>
<1,700>
<6,900>
5.46
4,700
18,600
6.18
5,300
21,100
<3.85>
<3,300>
<13,100>
<4.20>
<3,600>
<14,300>
11.17
9,600
38,100
12.50
10,800
42,700
Note:
1 Cooling : Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB/24˚CWB
2 Heating : Indoor 20˚CDB/13.8˚CWB, Outdoor 7˚CDB/16˚CWB
Page80
LOSSNAY
The OA Processing Unit is equipped with a new permeable film humidifier
developed and patented by Mitsubishi Electric. Steam transmission efficiency
has been improved remarkably by lowering the resistance of the material. The
use of a 3-layer film that allows only the transfer of steam prevents the
production of white powder, so there is no need for the use of a water purifier.
The OA (outdoor-air) Processing Unit creates an optimum indoor-air environment at an unparalleled rate of cost
efficiency providing substantial energy savings. Forced air ventilating and humidifying functions unique to this system
keep indoor-air fresh and free of contaminants preventing “sick building syndrome” and the spread of airborne viruses
such as the flu. Another novel feature of the OA Processing Unit is the “Lossnay core, a heat-exchange unit that
functions to transfer heat efficiently, cutting ventilation load by as much as 70%. This special combination of functionality
and performance designed to ensure users ample comfort and year-round health which cannot be found anywhere else
on the market.
GUF-50RD(H)
3
*1
Cooling Capacity
5.46 (DX coil:3.63, Lossnay:1.83)KW
Heating capacity
6.18 (DX coil:4.17, Lossnay:2.01)KW
500m
3
/h Single phase 220-240V 50Hz
GUF-100RD(H)
3
*1
Cooling Capacity
11.17 (DX coil:7.32, Lossnay3.85)KW
Heating capacity
12.50 (DX coil:8.30, Lossnay:4.20)KW
1000m
3
/h Single phase 220-240V 50Hz
*1 H : Humidifying Type
New Permeable Film Humidifier (RDH3 model)
Outdoor
air
Ultra-water
repellant
cell-based
water-vapor
transmission
filter
Water
Ultra-water
repellant
cell-based
water-vapor
transmission
filter
Water
Steam
New filter
3-dimensional
cloth
Spacer
Humidified air
OA Processing
Units
Air filter
Prevents clogs in
the Lossnay Core.
DX Heat exchanger
Cools or heats the drawn
in outdoor-air.
SA (Supply air)
The processed, fresh
outdoor-air is vented
to the indoor rooms.
RA (Return air)
The exhaust
fan draws in
contaminated
indoor-air.
EA
(
Exhaust air
)
Heat from the indoor air (both sensible
and latent) is recovered by the Lossnay
Core and vented outside by the
exhaust fan.
The exhaust fan
High efficiency filters (Option)
The supply fan
Maintenance cover
OA
(
Outdoor air
)
Fresh, outdoor-air in a quantity
required for ventilation is drawn
in by the supply fan.
Heat recovery unit
(Lossnay Core)
Temperature and humidity are
exchanged between the supply
air and the exhaust air.
Comfortable Level of Humidity for Exceptionable
Air Quality
Improvements in the system of airflow patterns and water injection techniques
have resulted in a substantial increase in humidifying volume.
Highly Efficient Humidification
Ideal Indoor-Air Quality — For Your Comfort and Health
Page79
Indoor unit
Page view 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 68 69

Comments to this Manuals

No comments