Mitsubishi SR-SD1 Specifications Page 130

  • Download
  • Add to my manuals
  • Print
  • Page
    / 141
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 129
APPENDIX 3 EMC INSTALLATION GUIDELINES
5. Measures for Wiring in Panel
124
5. Measures for Wiring in Panel
Cables act as antennas to propagate unnecessary noise, and thus must be appropriately shielded and
treated. The following measures must be sufficiently considered for the cables
(SH21/F010/FCUA-R211) that carry out high-speed communication.
5.1 Precautions for Wiring in Panel
(1) If the cables are led unnecessary in the panel, they will be contaminated by noise. Thus, keep the
device layout and wiring length as short as possible.
Device
Noise
Device
Device Device Device Device
(2) Always connect the grounding wire to the FG terminal indicated on the device.
(3) Keep the distance between the power cable and detector cable to the drive section motor as far
apart as possible when wiring.
(4) Do not lead the power wire around the panel without using a filter.
Device
Radiated
Noise
AC input
Partition plate
NF
Noise
Noise
filter
Page view 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 140 141

Comments to this Manuals

No comments