CHAPTER 3 INSTALLATION
3.1 General Specification
8
Type name
FCU6-DX210
FCU6-DX211
FCU6-DX330
FCU6-DX331
FCU6-DX340
FCU6-DX341
FCU6-DX220
FCU6-DX221
FCU6-DX430
FCU6-DX431
FCU6-DX440
FCU6-DX441
FCU6-DX310
FCU6-DX311
FCU6-DX320
FCU6-DX321
FCU6-DX410
FCU6-DX411
FCU6-DX420
FCU6-DX421
Unit name Base I/O unit
During operation 0~55°C
Ambient
temperature
During storage
20~60°C
During operation 45~75% RH (with no dew condensation)
Ambient
humidity
During storage 45~80% RH (with no dew condensation)
Vibration resistance 0.5G or less (during operation)
Shock resistance 3G or less (during operation)
General specifications
Working atmosphere No corrosive gas, dust and oil mist
Power voltage
24VDC±5%
Ripple ±5% (P-P)
Power
s
p
ecifications
Current consumption 3.6A 4.8A 5.0A 6.2A
Heating value (max.)
35W (3) 45W (3) 50W (3) 60W (3)
Weight 2.0kg
Unit size Refer to appendix.
(3) Heating value for when all DI/DO points are ON.