H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.
In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Check the resistance of fan motor. (Refer to
11-4.)
Is the resistance of
fan motor normal?
Replace the outdoor
fan motor.
Disconnect the connector CN771 on the
inverter P.C. board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION
INDICATOR lamp on
the indoor unit light up?
After 3 minutes, is
there voltage 230 VAC
between CN771 and
on the inverter P.C.
board?
Replace the outdoor
fan motor.
Replace the inverter
P.C. board.
Yes
No
Yes
No
I Check of outdoor fan motor