3. Outdoor unit failure mode table
The upper
lamp of
OPERATION
INDICTOR
lamp (Indoor
unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
Condition Correspondence
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
OFF None (Normal)
——
2-time ash
2.5 seconds
OFF
Outdoor power system
Over current protection stop is
continuously performed 3 times within
1 minute after the compressor gets
started.
• Reconnect connectors.
• Refer to 11-5. ”How
to check inverter/
compressor”.
• Check stop valve.
○○
3-time ash
2.5 seconds
OFF
Discharge temperature
thermistor
1-time ash every
2.5 seconds
Thermistor shorts or opens during
compressor running.
• Refer to 11-5. ”Check
of outdoor thermistors”
.
Defective outdoor
thermistors can be
identi ed by checking
the blinking pattern of
LED.
○○
Defrost thermistor
Fin temperature thermistor 3-time ash 2.5
seconds OFF
P.C. board temperature
thermistor
4-time ash 2.5
seconds OFF
4-time ash
2.5 seconds
OFF
Overcurrent 11-time ash 2.5
seconds OFF
12 A (HC25) / 14 A (HC35) current ow
into intelligent power module.
• Reconnect compressor
connector.
• Refer to 11-5. ”How
to check inverter/
compressor”.
• Check stop valve.
Compressor synchronous
abnormality (Compressor
start-up failure protection)
12-time ash 2.5
seconds OFF
Waveform of compressor current is
distorted.
• Reconnect compressor
connector.
• Refer to 11-5. ”How
to check inverter/
compressor”.
5-time ash
2.5 seconds
OFF
Discharge temperature
Temperature of discharge temperature
thermistor exceeds 116°C, compressor
stops. Compressor can restart if
discharge temperature thermistor reads
100°C or less 3 minutes later.
• Check refrigerant
circuit and refrigerant
amount.
• Refer to 11-5. ”Check
of LEV”.
6-time ash
2.5 seconds
OFF
High pressure
Temperature of indoor coil thermistor
exceeds 70°C in HEAT mode. When
defrost thermistor exceeds 70°C in
COOL mode.
• Check refrigerant
circuit and refrigerant
amount.
• Check stop valve.
7-time ash
2.5 seconds
OFF
Fin temperature/ P.C. board
temperature
7-time ash 2.5
seconds OFF
Temperature of n temperature
thermistor on the inverter P.C.
board exceeds 82°C (HC25) / 83°C
(HC35), or temperature of P.C. board
temperature thermistor on the inverter
P.C. board exceeds 81°C (HC25) / 85°
C (HC35).
• Check around outdoor
unit.
• Check outdoor unit air
passage.
• Refer to 11-5. ”Check
of outdoor fan motor”.
9-time ash
2.5 seconds
OFF
Nonvolatile memory data 5-time ash 2.5
seconds OFF
Nonvolatile memory data cannot be
read properly.
• Replace the inverter
P.C. board.
○○
10-time ash
2.5 seconds
OFF
Discharge temperature
Temperature of discharge temperature
thermistor has been 50°C or less for 20
minutes.
• Refer to 11-5. ”Check
of LEV”.
• Check refrigerant
circuit and refrigerant
amount.
11-time ash
2.5 seconds
OFF
DC voltage 8-time ash 2.5
seconds OFF
DC voltage of inverter cannot be
detected normally.
• Refer to 11-5. ”How
to check inverter/
compressor”.
Each phase current of
compressor
9-time ash 2.5
seconds OFF
Each phase current of compressor
cannot be detected normally.
12-time ash
2.5 seconds
OFF
Overcurrent Compressor
open-phase
10-time ash 2.5
seconds OFF
12 A (HC25) / 14 A (HC35) current ow
into intelligent power module (IPM).
When the open-phase operation of
compressor is detected. When the
interphase short out occurs in the
output of the intelligent power module
(IPM). When the compressor winding
shorts out.
• Reconnect compressor
connector.
• Refer to 11-5. ”How
to check inverter/
compressor”.
14-time ash
2.5 seconds
OFF
Stop valve (Closed valve) 14-time ash 2.5
seconds OFF
Closed valve is detected by compressor
current.
• Check stop valve.
○○
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).